600/1000V, LSOH Insulated LSOH Sheathed Unarmoured Power and Control Cables

FGD400 1HH-F (CU/LSOH/LSOH 600/1000V Class 5)

Application

The cables are mainly used in public buildings, plant engineering, industrial machinery, heating and air-conditioning systems, particularly where human and animal life as well as valuable property are exposed to high risk of fire hazard.

Standards

Basic design adapted to EN 50525-3-11

Fire Performance

600/1000V, LSOH Insulated LSOH Sheathed Unarmoured Power and Control Cables 600/1000V, LSOH Insulated LSOH Sheathed Unarmoured Power and Control Cables
Flame Retardance (Single Vertical Wire Test) IEC 60332-1
Halogen Free IEC 60754-1
Smoke emmision IEC 61034-1&2
No Corrosive Gas Emission IEC 60754-2

Cable Construction

Conductor Annealed copper wire, stranded according to BS EN 60228 class 5.
Insulation Halogen free compound.
Inner Covering(Option) Extruded or lapped.
Outer Sheath Flame retardant, UV resistance, cold resistance LSOH compound.
Protective conductor G = with GN-YE protective conductor X = without protective conductor

Colour Code

Color coded accoding to VDE 0293-308

No. of cores Colour of coresb
Protective Live
3 Cores Yellow/Green Blue Brown
4 Cores Yellow/Green - Brown Black Grey
4 Coresa Yellow/Green Blue Brown Black
5 Cores Yellow/Green Blue Brown Black Grey

a For certain applications only.

b In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire, is not regarded as a core. A concentric conductor is identified by its position and, therefore, need not be identified by colou.

From 6 cores: black with white numbers.

Cables and cords without a green-and-yellow cores

No. of cores Colour of coresb
2 Cores Blue Brown
3 Cores - Brown Black Grey
3 Coresa Blue Brown Black
4 Cores Blue Brown Black Grey
5 Cores Blue Brown Black Grey Black

a For certain applications only.

b In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire,is not regarded as a core. A concentric conductor is identified by its position and, therefore, need notbe identified by colou.

Sheath color. generally black

Physical And Thermal Properties

Temperature range -15°C - 70°C(flexing) ; -40°C - 80°C(fixed installation)
Rated voltage 600/1000V
Test voltage 4000V
Minimum bending radius 15 x outer diameter(flexing) ; 4 x outer diameter(fixed installation)

Construction Parameters

No. of Core X Cross Section Nominal Overall Diameter Approx. Weight No. of Core X Cross Section Nominal Overall Diameter Approx. Weight
mm2 mm mm mm2 mm mm
2 x 1.0 8.6 107 4 G 2.5 12.2 262
3 G 1.0 9.0 123 5 G 2.5 13.3 307
4 G 1.0 9.6 144 7 G 2.5 14.4 390
5 G 1.0 10.4 167 12 G 2.5 18.7 624
7 G 1.0 11.1 206 18 G 2.5 22.0 879
12 G 1.0 14.0 314 25 G 2.5 25.8 1212
18 G 1.0 16.1 428 3 G 4 12.6 290
25 G 1.0 18.6 569 4 G 4 13.7 351
2 x 1.5 9.6 137 5 G 4 14.9 416
3 G 1.5 10.1 161 3 G 6 13.9 377
4 G 1.5 10.8 190 4 G 6 15.1 463
5 G 1.5 11.7 221 5 G 6 16.8 559
7 G 1.5 12.6 276 7 G 6 19.3 714
12 G 1.5 16.1 427 4 G 10 18.7 757
18 G 1.5 18.8 596 5 G 10 20.7 915
25 G 1.5 21.7 799 7 G 10 22.1 1065
2 x 2.5 10.8 184 4 G 16 21.3 1070
3 G 2.5 11.3 219 5 G 16 23.6 1296

 

Note : Other sizes are available upon request.