6.35/11kV Screened ABC –Aerial Bundled Cables to AS/NZS 3599.1 (AL/XLPE /CWS/HDPE)

Application

Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

Standard

AS/NZS 3599.1

Construction

Phase Conductor Circular compacted stranded H68 aluminium to BS2627.
Conductor Screen Extruded semi-conductive layer.
Insulation XLPE.
Insulation Screen Extruded semi-conductive layer.
Metallic Screen Copper wire screen.
Separator Semi-conductive swellable tape.
Outer Sheath HDPE.
Support Conductor Galvanized steel wires.
Assembly Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

Dimensions

number of cores x nominal cross section Nominal conductor diameter Nominal insulation thickness Nominal insulation screen thickness Copper wire screen stranding Nominal sheath thickness Galvanized steel wire stranding Nominal overall diameter Weight Continuous current rating, A
Still air 1m/s wind 2m/s wind
mm^2 mm mm mm No/mm mm No/mm mm kg/km A A A
Light duty screen
3x35 6.9 3.4 0.8 25/0.85 1.8 7/2.00 54.1 1820 99 140 165
3x35 6.9 3.4 0.8 25/0.85 1.8 19/2.00 58.1 2130 100 145 165
3x50 8.1 3.4 0.8 25/0.85 1.8 19/2.00 60.4 2300 120 170 200
3x70 9.7 3.4 0.8 25/0.85 1.8 19/2.00 63.6 2570 150 215 250
3x95 11.4 3.4 0.8 25/0.85 1.8 19/2.00 67.0 2900 180 260 305
3x120 12.8 3.4 0.8 25/0.85 1.8 19/2.00 69.8 3190 205 300 355
3x150 14.2 3.4 0.8 25/0.85 1.9 19/2.00 73.0 3530 235 340 400
3x185 15.7 3.4 0.8 25/0.85 1.9 19/2.00 76.0 3890 265 390 460
Heavy duty screen
3x35 6.9 3.4 0.8 40/0.85 1.8 7/2.00 54.1 2050 99 140 165
3x35 6.9 3.4 0.8 40/0.85 1.8 19/2.00 58.1 2360 100 145 165
3x50 8.1 3.4 0.8 23/1.35 1.8 19/2.00 62.4 2820 120 175 200
3x70 9.7 3.4 0.8 32/1.35 1.8 19/2.00 65.6 3440 150 215 250
3x95 11.4 3.4 0.8 39/1.35 1.8 19/2.00 69.0 4030 180 260 305
3x120 12.8 3.4 0.8 39/1.35 1.8 19/2.00 71.8 4320 205 300 355
3x150 14.2 3.4 0.8 39/1.35 1.9 19/2.00 75.0 4670 230 340 400
3x185 15.7 3.4 0.8 39/1.35 1.9 19/2.00 78.0 5020 265 390 460