ProfiNet Type B
Application
Industrial Ethernet ProfiNet cables are designed to provide reliable network communications in the demanding Industrial and Process Control environment where difficult EMC conditions are pervasive. Conforming to the EIA/TIA-568 standard, These Cables support half-duplex high speed communications.It ensures superior transmission properties and can be used even under most severe conditions.
Construction
Type/Area of Application |
Mobile Use |
Cable Construction |
2x2x0.64 mm (stranded) + 4x1.5 mm2 |
Inner Conductor Diameter 1 |
Copper, tinned (AWG 22/7) |
Inner Conductor Diameter 2 |
Copper, bare (AWG 16/84) |
Conductor Insulation 1 |
Foam-Skin-PE |
Conductor Insulation 2 |
Foam-Skin-PE |
Conductor Colors 1 |
white, yellow, blue, orange |
Conductor Colors 2 |
Black |
Stranding Element |
Double Conductor |
Shielding 1 |
Polyester foil over stranded bundle |
Shielding 2 |
Polyester foil, aluminum lined |
Total Shielding |
Polyester foil |
Outer Jacket Material |
FRNC |
Outer Diameter |
10.3 mm ± 0.3 mm |
Outer Jacket Color |
Green |
Electrical Data
Characteristic Impedance@1-100 MHz |
100 Ω ± 15 Ω |
|
Conductor Resistance |
60.0 Ohm/km max. |
|
Insulation Resistance |
0.50 GOhm x km min. |
|
Mutual Capacitance |
52.0 nF/km nom. |
|
Working Voltage |
300V |
|
Test Voltage |
1.5 KV |
|
Attenuation |
10 MHz |
6.3 dB/10m |
16 MHz |
8.0 dB/10m |
|
62.5 MHz |
16.5 dB/10m |
|
100 MHz |
21.3 dB/10m |
Technical Data
Weight |
approximately 153.0 kg/km |
Min. Bending Radius for Laying |
10 x OD mm |
Operating Temperature Range, min. |
-40 °C |
Operating Temperature Range, max. |
+70 °C |