Profibus L2 Outdoor + Industry

Application

This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial field bus systems are used. The types mentioned here are suitable for outdoor laying (PE jacket) and industry laying (PUR jacket).

Construction

Type/Area of Application

Fixed Installation, Outdoor /Heavy Duty

Cable Construction

1x2x0.64 mm

Inner Conductor Diameter

Copper, bare (AWG 22/1)

Conductor Insulation

Foam-skin-PE

Conductor Colors

Red, green

Stranding Element

2 conductors + 2 fillers stranded together

Shielding 1

Polyester foil over stranded bundle

Shielding 2

Polyester foil, aluminum-lined

Total Shielding

Cu braid, tinned

Outer Jacket Material

PE/PUR

Outer Diameter

8.0 mm ± 0.4 mm

Outer Jacket Color

Black

Electrical Data

Characteristic Impedance @ 3-20Hz

150 Ω ± 10 Ω

Conductor Resistance

55.0 Ohm/km max.

Insulation Resistance

1.00 GOhm x km min.

Mutual Capacitance @ 1 KHz

30.0 nF/km nom.

Working Voltage

 Max: 250 V

Test Voltage

1.5 kV

Attenuation

9.6

kHz

2.5

dB/km

38.4

kHz

4.0

dB/km

4.0

MHz

22.0

dB/km

16.0

MHz

42.0

dB/km

Technical Data

Weight:

approximately 66.0 kg/km

Min. Bending Radius (Laying)

15 x OD mm

Operating Temp.Range, min.

-40 °C

Operating Temp.Range, max.

+70 °C