EN50288-7 |
|||
EN 50288-7 Cables
PE Insulated, PVC Sheathed, Individual and Overall Screened & Double Steel Tape Armoured Instrumentation Cables (Multipair)
RE-2Y(St)YDSTAY PIMF 90°C / 300V
APPLICATION
For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply. Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral. Recommended for use as fire protection messure for people and important material assets.
STANDARDS
Basic design to EN 50288-7
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires& cable test)*** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard, *** denotes optional.
VOLTAGE RATING
300V
CABLE CONSTRUCTION
- Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
- Insulation: PE compound as per EN 50290. 2-23.
- Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
- Binder tape: Polyester (PEPT) Tape
- Individual Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm², covered with extruded PVC.
- Binder tape: Polyester (PEPT) Tape
- Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
- Inner Sheath: PVC compound as per EN 50290-2-22.
- Amouring: Double steel tape armour
- Outer Sheath: Thermoplastic PVC compound as per EN 50290-2-22. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
- Insulation: Red / White
- Outer Sheath: Gray
PHYSICAL and THERMAL PROPERTIES
- Temperature Range During Operation (Fixed State): -30°C – +70°C
- Temperature Range During Installation (Mobile State): -5°C – +50°C
- Minimum Bending Radius: 10 X Overall Diameter
- Sunlight Resistance: UL 1581 section 1200
- Oil Resistance: ASTM No: 2 (7 HRS 90°C)
ELECTRICAL ROPERTIES
Conductor Area Size | mm2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 |
Insulation thickness (nominal) | mm | 0.4 | 0.4 | 0.4 | 0.45 | 0.45 |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | ||||
Individual conductors | 1G | |||||
Individual screens | 1M | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | <150 | ||||
Inductance | mH/km (Max.) | 1 | ||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 |
Test Voltage | V (1min) | |||||
AC | 2000 | |||||
DC | 3000 |
CONSTRUCTION PARAMETERS
Caledonian Cable Code | RE-2Y(St)YDSTAY PiMF | ||||||||
No. of Pairs x2xCross Section | Nominal Insulation Thick-ness | Nominal Inner Sheath Thick-ness | Nominal Overall Diameter Over Inner Sheath | Nominal Armour Steel Tape Thick -ness |
Nominal Overall Diameter Over Armour |
Nominal Outer Sheath Thick-ness | Nominal Overall Diameter | Approx. Weight | |
No.x2xmm2 | mm | mm | mm | mm | mm | mm | mm | kg/km | |
RE-2Y(St)YDSTAY PiMF 2P1.5 |
2x2x1.5 | 0.6 | 1.2 | 14.0 | 0.2 | 14.8 | 1.5 | 17.8 | 390 |