6192Y/ 6193Y to BS 6004

Application and Description

These cables are suitable for fixed installation in dry or damp premises on walls, boards or trays, in channels or embedded in plaster. They should be laid in conduit in conduit or trunking where mechanical protection is required.

Cable Construction

  • - Fine bare copper strands
  • - Stranding to BS 6360, IEC 60228 CL-1 or 2
  • - PVC insulation type TI1 to BS 7655
  • - PVC sheath type T6 to BS 7655

Core Identification

  • 2 cores: brown and blue
  • 3 cores: brown, black and grey

Technical Characteristics

  • - Working voltage: 300/500 volts
  • - Test voltage: 2000 volts
  • - Minimum bending radius: 4xOverall diameter
  • - Operating temperature: -15o C to +70o C
  • - Short circuit temperature: +160o C
  • - Flame retardant: IEC 60332.1
  • - Insulation resistance: 10 MΩxkm

Cable Parameter

AWG
(No of Strands/
Strand Diameter)
No. of Cores x
Nominal Cross
Sectional Area
#xmm^2
Nominal
Thickness of
Insulation
mm
Nominal
Thickness of
Sheath
mm
Nominal overall
dimensions
Nominal
Weight
kg/km
lower limit
mm
upper limit
mm
6192Y
17 2 × 1.0 0.6 0.9 4x6.2 4.7x7.4 53
16 2 × 1.5 0.7 0.9 4.4x7.0 5.4x8.4 70
14 2 × 2.5 0.8 1 5.2x8.4 6.2x9.8 105
12(7/20) 2 × 4 0.8 1 6x10.4 7.2x11.5 150
10(7/18) 2 × 6 0.8 1.1 6.8x11.5 8.0x13.0 205
8(7/16) 2 × 10 1 1.2 7.8x15.1 9.6x16 325
6(7/14) 2 × 16 1 1.3 9.8x17.2 11.0x18.5 465
6193Y
17 3 × 1.0 0.6 0.9 4x8.4 4.7x9.8 77
16 3 × 1.5 0.7 0.9 4.4x9.8 5.4x11.5 100
14 3 × 2.5 0.8 1 5.2x11.5 6.2x13.5 150
12(7/20) 3 × 4 0.8 1.1 6x14.8 7.4x16.5 230
10(7/18) 3 × 6 0.8 1.1 6.8x16.5 8.0x18.0 300
8(7/16) 3 × 10 1 1.2 7.8x21.0 9.6x22.5 485
6(7/14) 3 × 16 1 1.3 9.8x24.8 11.0x26.5 700