6591TQ to BS 6883

Application and Description

These cables are designed for use in offshore applications where mechanical protection is not required. Examples of application include fixed wiring in ships and fixed offshore drilling rigs and oil platforms.

Cable Construction

  • - Fine bare copper strands
  • - Stranding to BS 6360 CL-5 or IEC 60228 CL-5
  • - EPR(Ethylene Propylene Rubber) rubber insulation to BS 7655
  • - TPBWB (Tinned phosphor bronze wire braid) non-magnetic armour
  • - LSOH (Low Smoke Zero Halogen), type SW4 to BS 7655

Core Identification

1 core: Black or red

Technical Characteristics

  • - Working voltage: 600/1000 volts
  • - Test voltage: 3500 volts
  • - Minimum bending radius: up to 10mm^2 - 3xOverall diameter
    10mm^2-25mm^2 - 4xOverall diameter
    Above 25mm^2 - 6xOverall diameter
  • - Temperature Range: -25o C to +85o C
  • - Oxygen Index32%, HCL 5%
  • - Flame retardant: IEC 60332.3

Cable Parameter

AWG
(No of Strands/
Strand Diameter)
No. of Cores x
Nominal Cross
Sectional Area
#xmm^2
Nominal
Thickness of
Insulation
mm
Nominal
Thickness
of
Bedding
mm
Diameter
of Braid
Wire
mm
Nominal
Thickness of
Sheath
mm
Nominal
Overall
Diameter
mm
Nominal
Weight
kg/km
17(7/26) 1x1.0 0.8 1 0.3 1 8.8 135
16(7/24) 1x1.5 0.8 1 0.3 1.1 9.3 145
14(7/22) 1x2.5 0.8 1 0.3 1.1 9.8 165
12(7/20) 1x4 1 1 0.3 1.1 10.8 190
10(7/18) 1x6 1 1 0.3 1.1 11.4 225
8(7/16) 1x10 1 1 0.3 1.2 13.1 315
6(7/14) 1x16 1 1 0.3 1.2 14.2 395
4(7/12) 1x25 1.2 1.2 0.3 1.3 16.7 565
2(7/10) 1x35 1.2 1.2 0.3 1.4 17.8 670
1(19/13) 1x50 1.4 1.4 0.3 1.4 19.7 865
2/0(19/11) 1x70 1.4 1.4 0.3 1.5 22.1 1120
3/0(19/10) 1x95 1.6 1.6 0.3 1.6 24.4 1440
4/0(37/12) 1x120 1.6 1.6 0.3 1.7 26.6 1780
300MCM
(37/11)
1x150 1.8 1.8 0.3 1.8 28.9 2120
350MCM
(37/10)
1x185 2 2 0.45 1.9 32.5 2700
500MCM
(61/11)
1x240 2.2 2.2 0.45 2 36 3410
-(61/10) 1x300 2.4 2.4 0.45 2.2 39.4 4180
-(61/9) 1x400 2.6 2.6 0.45 2.3 43.9 5280
-(61/8) 1x500 2.8 2.8 0.45 2.5 48.1 6480
-(127/10) 1x630 2.8 2.8 0.45 2.6 52.3 7820