RHH/RHW-2/USE-2, FR-EPR, 600V

Application

RHH/RHW-2/USE-2, FR-EPR type is for use in broad range of commercial, industrial and utility applications where reliability is the major concern, where maximum performance will be demanded and where space is limited, and usually used in free air, raceways or direct burial in accordance with NEC.

Compliances

  • National Electrical Code (NEC)
  • UL 44 Type RHH/RHW-2
  • UL 854 Type USE-2
  • ICEA S-95-658/NEMA WC70)
  • “FOR CT USE” on 1/0 AWG and larger in accordance with NEC
  • UL Listed VW-1
  • UL 1581 VW-1
  • For 1/0 AWG and larger: IEEE 383, IEEE 1202/CSA FT4, ICEA T-29-520
  • OSHA acceptable

Construction

RHH/RHW-2/USE-2, FR-EPR, 600V
Conductor Compressed stranded annealed bare copper, Class B stranding per ASTM B8
Insulation Flame-retardant Ethylene Propylene Rubber (EPR)
Color Upon request, black is preferable

Parameters

AWG or kcmil Strand Conductor Diameter Nominal Insulation Thickness Nominal Overall Diameter Copper weight Cable Weight
Inch/mm Inch/mm Inch/mm Lbs/kft kg/km Lbs/kft kg/km
14 7 0.07 1.78 0.045 1.14 0.17 4.32 13 19 24 36
12 7 0.09 2.29 0.045 1.14 0.19 4.83 20 30 33 49
10 7 0.12 3.05 0.045 1.14 0.21 5.33 32 48 48 71
8 7 0.15 3.81 0.060 1.52 0.27 6.86 50 75 78 116
6 7 0.18 4.57 0.060 1.52 0.31 7.87 81 121 114 170
4 7 0.23 5.84 0.060 1.52 0.36 9.14 129 192 169 252
2 7 0.29 7.37 0.060 1.52 0.42 10.67 205 305 254 378
1/0 19 0.37 9.40 0.080 2.03 0.53 13.46 326 485 402 598
2/0 19 0.41 10.41 0.080 2.03 0.58 14.73 411 612 500 744
4/0 19 0.52 13.21 0.080 2.03 0.69 17.53 653 972 759 1130
250 37 0.56 14.22 0.095 2.41 0.77 19.56 772 1149 905 1347
350 37 0.67 17.02 0.095 2.41 0.87 22.10 1081 1609 1235 1838
500 37 0.80 20.32 0.095 2.41 1.00 25.40 1542 2295 1728 2572
750 61 0.98 24.89 0.110 2.79 1.22 30.99 2316 3447 2573 3829
1000 61 1.13 28.70 0.110 2.79 1.37 34.80 3086 4593 3402 5063