Instrumentation Cables | ||||||||||||||||
Instrumentation Cables
Defence Standard-C Cables
7-2-6C SCREENED |
||||
Product Name/Code: 7-2-6C SCREENED |
Electrical Performance |
|||
Application: |
Max.Conductor DC Resistance at 20 ℃(Ω/Km) 22.49 |
<84.80 |
||
Multi-conductor-audio, control & Instrumentation Cables. |
Operating Temperature( ℃ ) 74 |
80 |
||
Construction |
Voltage Rating(V) 1499 |
30 |
||
6 Core |
Stranded Tinned Copper |
20 ℃ Insulation Resistance(M Ω .KM) |
> 200 |
|
AWG |
24 |
|||
Construction |
T0.20 x 7 |
|||
Conductor Diameter (mm) 0.20 |
0.60 |
|||
Insulation |
PVC |
|||
Thickness |
0.3 |
|||
Insulation Diameter(mm) |
1.20 |
|||
Mylar Spiral twist(over lapping,%) |
>=25% |
|||
Screening |
Tinned Copper |
|||
Construction(mm) |
T0.15 x 16 x5 |
|||
Coverage Area(%) |
> 70% |
|||
Nylon rip cord |
210D |
|||
Sheathing |
PVC OR LSF |
|||
Thickness(mm) |
0.88 |
|||
Diameter(mm) |
5.90 |
|||
Sheathing Compound |
PVC/LSF/LSOH |
|||
Core Identification/Color Code |
According to customer request |
|||
Bending Radius |
6xOverall Diameter |
|||
Temperature Rating |
70C |
|||
Voltage Rating |
300/500V |
|||
Fire Performance |
||||
Flame Propagation Test to IEC 60332 Part 1 and Part 3 |
||||
Website: www.addison-cables.com |
||||
E-mail: sales@addison-cables.com |