Instrumentation Cables | ||||||||||||||||
Instrumentation Cables
1. ESI 0.9-6(1-0.8)
Constructional & Electrical Performance Data
ESI 09-6 Issue 6 Section 3 – Induced Voltage Control Cable
Conductors
0.80mm Plain annealed copper wire in accordance with BS6360 Class 1.
Insulation
The conductors are insulated with Polyvinyl Chloride Type 02 to BS7655, uniformly twisted together to form a pair with a
maximum lay length of 125mm, and colour coded for identification (See Table 1). Suitable for voltages upto and including
150 Volts (d.c.) and 110 Volts (a.c.)
Cable Formation
2 pair cables are laid up in quad formation.
5 – 10 pair cables are laid up in layer formation.
20 – 200 pairs cables are laid up in 20 pair units to form the required cable size. A printed number on a longitudinal tape
applied under the binder tape identifies each unit.
Screens
For 2 pair cables the screen comprises of an aluminium foil in contact with a 0.80mm tinned copper drain wire. For 5 pairs and
above the screen comprises of an aluminium tape with a backing that ensures adhesion to the bedding. The tape screen is
applied over a ripcord and in contact with a 0.80mm tinned copper drain wire.
Note: Armoured cables (Generation) always require a collective screen. Types 1 & 2 can incorporate a
screen if required.
Outer Covering
Type 1 |
Unarmoured Multipair Light Current Control cables. |
Type 2 |
Armoured Multipair Light Current Control cables. |
Type 3 |
Armoured Multipair (Generation) Light Current Control cables. |
Alternative PVC materials producing lower levels of HCL are available on request.
Electrical Characteristics
High Voltage Test |
|
Collective screens |
2000 Volts for 1 minute between each conductors & earth |
Cables without screen |
10 000 Volts (ac) for 1 minute between each conductor & earth |
Conductor Resistance |
73.60Ohm/Km Loop @ 20°C (Max) |
Insulation Resistance |
80 Mohm/Km @ 20°C (Min) |
Capacitance Unbalance |
|
2 Pair |
800 pF/500 mtrs @ 1 kHz (Max) |
Mutual Capacitance |
Mutual Capacitance |
Mutual Inductance |
915 μH/500 mtrs @ 1 kHz (Max) |
Cable Dimensions & Identification
Type 1 cables ( Unarmored, Induced voltages up to 5kV)
Type 2 cables (Armoured)
Type 3 cables (Generation)