REXHOHR

Application

For transmission of analogue and digital signals in instrument and control systems; not allowed for direct connection to low impedance sources, e.g. public mains electricity supply.

Standard and Approval

  • CEI 20-11
  • IEC 60502-1
  • IEC 60332.3
  • EN50266-2

Cable Construction

  • Conductor: annealed copper wires acc. to class 2 of BS 6360
  • Insulation: PE
  • Colour core:(CEI unel 00725)
  • pair:blue-black, with black progressively numbered
  • Triad: blue-brown-black with black progressively numbered
  • Stranding: cores twisted in pairs-triads.pairs-triads twisted in layers
  • Screen: Individual: electrostatic screen of plastic and aluminium tape + tinned drain-wire;
                   Overall: electrostatic screen of plastic and aluminium tape + tinned drain-wire
  • Outer sheath: flame retardant pvc outer sheath, RZ quality.

Technical Characteristics:

  • Max. rated working temperature : +70 °C
  • Max. rated short circuit temperature: +160 °C
  • Min. bend radium:10XØ (cable diameter in mm)

PARAMETERS

No.of cores
x cross section
n x mm2
Outer Ø
ca.mm
±10%
Cable
weight
approx.
kg/km
4x2x0.50 11.2 62
6x2x0.50 13.2 90
8x2x0.50 14.4 119
10x2x0.50 17.2 147
12x2x0.50 17.7 176
16x2x0.50 20.2 233
20x2x0.50 22.2 290
24x2x0.50 25.2 348
2x2x0.75 10.4 115
4x2x0.75 12 175
6x2x0.75 14 250
8x2x0.75 15.5 295
10x2x0.75 19 420
12x2x0.75 16.5 475
16x2x0.75 21.6 600
20x2x0.75 24.5 750
24x2x0.75 27 875
2x2x1 11.2 135
4x2x1 13 205
6x2x1 15.3 294
8x2x1 17.3 380
10x2x1 20.6 495
20x2x1 26.5 895
2x2x1.5 13 170
4x2x1.5 15 275
6x2x1.5 19.2 455
8x2x1.5 21 540
10x2x1.5 24.8 700
20x2x1.5 32 1255

Other constructions and sizes are available on request.