Fire resisting Cable | |||
450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (2-4 Cores)
FTX200 07RCZ1-R (CU/XLPE/CUTO/LSZH 450/750V Class 2)
APPLICATION
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical
plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design adapted to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)
|
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
|
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)
|
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
|
Halogen Free
|
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;
CEI 20-37/2-1 ; BS 6425-1*
|
No Corrosive Gas Emission
|
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;
CEI 20-37/2-2 ; BS 6425-2*
|
Minimum Smoke Emission
|
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
|
No Toxic gases
|
NES 02-713; NF C 20-454
|
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Filler, binder (if any): PP, PET, LSZH
Overall Screen: Copper tape
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.).
UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation Colour as per BS7671
|
With Earth Conductor
|
Without Earth Conductor
|
2Cores
|
-
|
Brown, Blue
|
3Cores
|
Yellow/Green, Brown, Blue
|
Brown, Gray, Black
|
4Cores
|
Yellow/Green, Brown, Gray, Black
|
Brown, Gray, Black, Blue
|
5Cores
|
Yellow/Green, Brown, Gray, Black, Blue
|
Brown, Gray, Black, Blue, Black
|
Above 5 Cores
|
Yellow/Green, Black Numbered
|
Black Numbered
|
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature Range During Operation: -30°C – +90°C
Temperature Range During Installation: -5°C – +50°C
Minimum Bending Radius: 6 x Overall Diameter
Electrical PROPERTIES
Dielectric test:
|
2500 V r.m.s. x 5’ (core/core)
|
Insulation resistance
|
≥1000 MΩ x km (at 20°C)
|
Short circuit temperature
|
250°C
|
CONSTRUCTION PARAMETERS
Conductor
|
FTX200 07RCZ1-R
|
|||||||
No. of
Core X
Cross Section
|
No./Nominal
Diameter of
Strands
|
Nominal
Overall
Diameter
Conductor
|
Nominal
Insulation
Thickness
|
Nominal
Copper Tape
Thickness
|
Nominal
Sheath
Thickness
|
Nominal
Overall
Diameter
|
Max.DC resistance of conductor @20°C
|
Approx.
Weight
|
Noxmm2
|
No./mm
|
mm
|
mm
|
mm
|
mm
|
mm
|
Ω/km
|
kg/km
|
2x1.0
|
7/0.44
|
1.32
|
0.7
|
0.1
|
1.2
|
10.7
|
18.1
|
172
|
2x1.5
|
7/0.53
|
1.59
|
0.7
|
0.1
|
1.3
|
11.3
|
12.1
|
197
|
2x2.5
|
7/0.67
|
2.01
|
0.7
|
0.1
|
1.3
|
12.2
|
7.41
|
239
|
2x4.0
|
7/0.85
|
2.55
|
0.7
|
0.1
|
1.3
|
13.4
|
4.61
|
300
|
3x1.0
|
7/0.44
|
1.32
|
0.7
|
0.1
|
1.3
|
11.2
|
18.1
|
194
|
3x1.5
|
7/O.53
|
1.59
|
0.7
|
0.1
|
1.3
|
11.8
|
12.1
|
224
|
3x2.5
|
7/0,67
|
2.01
|
0.7
|
0.1
|
1.3
|
12.8
|
7.41
|
276
|
3x4.0
|
7/0.85
|
2.55
|
0.7
|
0.1
|
1.3
|
14.1
|
4.61
|
353
|
4x1.0
|
7/0.44
|
1.32
|
0.7
|
0.1
|
1.3
|
12.0
|
18.1
|
224
|
4x1.5
|
7/0.53
|
1.59
|
0.7
|
0.1
|
1.4
|
12.7
|
12.1
|
261
|
4x2.5
|
7/0.67
|
2.01
|
0.7
|
0.1
|
1.3
|
13.9
|
7.41
|
326
|
4x4.0
|
7/0.85
|
2.55
|
0.7
|
0.1
|
1.3
|
15.3
|
4.61
|
422
|
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross-sectional
|
Reference Method 4 (enclosed in conduit in thermally insulating wall etc)
|
Reference Method 3 (enclosed in conduit on a wall or in trunking etc)
|
Reference Method 1 (clipped direct)
|
Reference Method 11 (on a perforated cable tray, horizontal or vertical)
|
Reference Method 12 (free air)
|
||||||
Horizontal flat
spaced
|
Vertical flat spaced
|
Trefoil
|
|||||||||
|
2
cables, single-phase
a.c. or
d.c.
|
3 or 4
cables,
3-phase
a.c.
|
2 cables, single-phase
a.c. or
d.c
|
3 or 4 cables, 3-phase a.c.
|
2 cables, single-phase a.c. or d.c. flat and touching
|
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
|
2 cables, single-phase
a.c. or
d.c. or flat and touching
|
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
|
2 cables, single-phase
a.c. or
d.c.
or 3 c
ables three phase
|
2 cables, single-phase
a.c. or
d.c.
or 3
cables three phase
|
3 cables, trefoil 3-phase a.c.
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.0
|
13
|
-
|
-
|
-
|
15
|
-
|
-
|
-
|
-
|
-
|
-
|
1.5
|
18
|
17
|
22
|
19
|
25
|
23
|
-
|
-
|
-
|
-
|
-
|
2.5
|
24
|
23
|
30
|
26
|
34
|
31
|
-
|
-
|
-
|
-
|
-
|
4
|
33
|
30
|
40
|
35
|
46
|
41
|
-
|
-
|
-
|
-
|
-
|
Voltage Drop (Per Amp Per Meter)
Nominal Cross
Section Area
|
2 cables d.c.
|
2 cables, single-phase a.c.
|
3 or 4 cables, 3-phase a.c.
|
|||
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1 and 11 (clipped direct or on trays touching)
|
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1,
|
Ref. Methods 1 and 11
|
||
11 and 12 (in trefoil)
|
(Flat and touching)
|
|||||
1
|
2
|
3
|
4
|
5
|
6
|
7
|
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
1.0
|
46
|
46
|
-
|
-
|
-
|
-
|
1.5
|
31
|
31
|
27
|
27
|
27
|
27
|
2.5
|
19
|
19
|
16
|
16
|
16
|
16
|
4
|
33
|
12
|
10
|
10
|
10
|
10
|
E-mail: uk@addison-cables.com |