NTSCGECWOEU Medium-Voltage Coal Cutter Cable
Applications
These cables are used for the connection of mobile electrical equipment inunderground mines, e.g. for coal-cutting machines,especially for the use in bretby chains with extremebending loads under low tensile stress.
Standards
VDE 0250 Part 813
Construction
System1 (1.8/3kV or 3.6/6kV): Flexible stranded tinned copper conductor with heatresistant3GI3 rubber based on EPR,easy strippable outer conductive layer.
System2 (0.6/1kV): Flexible stranded tinned copper conductor with heatresistant3GI3 rubber based on EPR.
Earth Conductor: Spiral of tinnedcopper.
Center Bundle: Control and pilot cores withcopper/steel conductors capable of expansion andcompression, EPR insulation,optional with fiber optics, covered with tinned copper wires semi conductive rubber sheath.
InnerSheath: 2 layer design, semi conductive rubber + Rubber type 5GM5.
Armour: Spiral of steel wires,embedded in the outer sheath, fiberglas tape which preventssheath exchanging.
Outer Sheath: Rubber type 5GM5, abrasion and tear resistant, oil resistant and flame retardant.
Dimensions and Weight
1.8/3kV
Number of Cores×Nominal Cross Section |
Minimium Overall Diameter |
Maximum Overall Diameter |
Nominal Weight |
No.×mm² |
mm |
mm |
kg/km |
3×50+3×(35+35/3)+2×(2×0.75ST)+2×0.75UEL |
62.0 |
66.0 |
7210 |
3×70+3×(50+50/3)+2×(2×0.75ST)+2×0.75UEL |
64.0 |
68.0 |
8200 |
3×95+3×(70+70/3)+2×(2×0.75ST)+2×0.75UEL |
74.0 |
78.0 |
10300 |
3.6/6kV
Number of Cores×Nominal Cross Section |
Minimium Overall Diameter |
Maximum Overall Diameter |
Nominal Weight |
No.×mm² |
mm |
mm |
kg/km |
3×35+3×(35+35/3)+2×(2×0.75ST)+2×0.75UEL |
66.0 |
72.0 |
7600 |
3×50+3×(50+50/3)+2×(2×0.75ST)+2×0.75UEL |
69.0 |
75.0 |
9200 |
3×70+3×(70+70/3)+2×(2×0.75ST)+2×0.75UEL |
76.0 |
81.0 |
11150 |
3×95+3×(95+95/3)+2×(2×0.75ST)+2×0.75UEL |
85.0 |
90.0 |
13300 |