Rubber & Crane Cables | |||||||||||||||||||
Rubber & Crane Cables
Coil End Lead to BS6195 Type 4
Options | |
CONSTRUCTION :
Conductor: Flexible Tinned Copper to BS6360
Insulation: Ethylene Propylene Rubber E.P.R ; Type FR1 (Voltage Categories A & C) & Type FR2 (Voltage Categories D & E) to BS 7655.
Sheath: Chlorosulphonated Polyethylene C.S.P. HOFR Black. To BS 6899
APPLICATION :
This range of Cables is designed as power leads for permanent connecton to coil winding motors, panel wiring and electrical machinery. They are able to withstand high temperature and immersion in varnish. Other applications include vehicle wiring. T he HOFR sheath resists oil and varnish and the stranding is designed as a compromise between flexibility and positional stability. Also suitable as an alternative to tri-rated and bi-rated cable in certain applications
TECHNICAL DATA :
Voltage Categories
A 300/500V
C 600/1000V
D 1900/3300V
E 3800/6600V
F 6350/11000V
Operating Temperature Range: -20oC to +70oC
Bending Radius: Up to 25mm2 = 6 x overall diameter
Above 25mm2 = 8 x overall diameter
SHEATH COLOUR :
0.5-10mm2: Red-Black
10mm2 above: Black only.
RELEVANT STANDARDS :
Cable in accordance with BS6195
Insulation & Sheath to BS6899
OPTIONS
Coiled end lead is also manufactured to BS6899 Type 5 - Silicon insulation 180oC Operating Temperature.
Voltage Category |
Maximum Equipment Test Voltage (ACrms) |
Nominal Voltage Rating of Cable Uo/U |
A |
2.5 |
300/500V |
C |
4.0 |
600/1000V |
D |
9.5 |
1900/3300V |
E |
17 |
3800/6600V |
Core and Size mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm for each voltage category |
||||||
Voltage Category |
Voltage Category |
||||||||
A |
C |
D |
E |
A |
C |
D |
E |
||
Mm |
mm |
|
|
|
|
|
|
|
|
0.5 |
16/0.2 |
0.8 |
1.4 |
- |
- |
3.3 |
4.5 |
- |
- |
0.75 |
24/0.2 |
0.8 |
1.4 |
- |
- |
3.5 |
4.7 |
- |
- |
1.0 |
32/0.2 |
0.8 |
1.4 |
- |
- |
3.7 |
4.9 |
- |
- |
1.5 |
30/0.25 |
0.8 |
1.4 |
- |
- |
4.0 |
5.2 |
- |
- |
2.5 |
50/0.25 |
0.9 |
1.4 |
2.8 |
- |
4.6 |
5.6 |
8.5 |
- |
4.0 |
56/0.3 |
1.0 |
1.4 |
2.8 |
- |
5.4 |
6.3 |
9.1 |
- |
6.0 |
84/0.3 |
1.0 |
1.5 |
2.8 |
- |
6.5 |
7.5 |
10.3 |
- |
10 |
80/0.4 |
1.2 |
1.5 |
2.8 |
- |
7.9 |
8.5 |
11.3 |
- |
16 |
126/0.4 |
- |
1.5 |
2.8 |
5.0 |
- |
9.6 |
12.4 |
17.2 |
25 |
196/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
11.4 |
13.8 |
18.6 |
35 |
276/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
12.8 |
12.5 |
20.0 |
50 |
396/0.4 |
- |
1.7 |
2.8 |
5.0 |
- |
14.8 |
17.1 |
22.1 |
70 |
360/0.5 |
- |
1.8 |
2.8 |
5.0 |
- |
17.2 |
19.2 |
24.2 |
95 |
475/0.5 |
- |
2.0 |
3.0 |
5.0 |
- |
19.2 |
22.0 |
26.3 |
120 |
608/0.5 |
- |
2.2 |
3.0 |
5.0 |
- |
21.9 |
23.5 |
27.8 |
150 |
756/0.5 |
- |
2.3 |
3.0 |
5.0 |
- |
24.1 |
25.5 |
29.8 |
185 |
925/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
26.3 |
27.5 |
32.1 |
240 |
1221/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
28.3 |
30.6 |
35.1 |
300 |
1525/0.5 |
- |
2.6 |
3.0 |
- |
- |
33.0 |
33.8 |
- |
400 |
2013/0.5 |
- |
2.8 |
3.0 |
- |
- |
37.4 |
37.8 |
- |
630 |
2106/0.6 |
- |
- |
3.2 |
- |
- |
- |
43.5 |
- |
Correction Factors
For ambient air temperatures other than 40°C, the following factors should be applied:
Ambient Air Temp |
Correction Factor |
1.140 |
1.100 |
1.050 |
1.000 |
0.945 |
0.900 |
0.835 |
0.775 |
0.705 |
0.603 |
0.545 |
0.445 |
Where cables are to be grouped in free air, the following factors should be applied:
No. of Cables in Group |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Correction Factor |
0.80 |
0.70 |
0.70 |
0.60 |
0.56 |
0.50 |
0.50 |
Ambient air temperature 40°C
Conductor operating temperature 90°C
Electrical Characteristics |
Resistance Values (ohms per kilometre)
Nominal Conductor Area |
Nominal Conductor Stranding |
Max. DC Resistance at 20°C |
Max. Continuous Current Ratings (BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |
Nominal Conductor Area |
Nominal Conductor Stranding |
Max. DC Resistance at 20°C |
Max. Continuous Current Ratings (BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |